Model AFS-222, AFS-262, and AFS-460 Differential Pressure Switches are general-purpose, airflow-proving switches designed for HVAC and building automation applications. They may be used to sense positive, negative, or differential air pressure.
The plated housing contains a diaphragm, calibration spring, and snap-acting switch (or switches). The pressure connections located on each side of the diaphragm accept 1/4" OD tubing via the integral compression ferrule and nut. An enclosure cover guards against accidental contact with the live-switch terminal screws and the set point-adjusting screw. The enclosure will accept a 1/2" conduit connection.
FEATURES
Two-year warranty
Adjustable set point
Knockout for 1/2" conduit
Enclosed terminals
SPECIFICATIONS
Set point range
AFS-222 0.05" W.C. to 12.0" W.C. (12.5 to 2989 Pa)
AFS-262 0.05" W.C. to 2.0" W.C. (12.5 to 498 Pa)
AFS-460 0.4" W.C. to 12.0" W.C. (99 to 2989 Pa)
AFS-460-DSS 2.0" W.C. to 12.0" W.C. (498 to 2989 Pa)
Switch differential (AFS-222, -262 only)
Progressive, increasing from approximately 0.02" W.C. (5.0 Pa)
@ min setpoint to approximately 0.8" W.C. (199.3 Pa) @ max setpoint
Contacts
AFS-222, -262 SPDT
AFS-460 SPST N.C.
AFS-460-DSS 2 SPST N.C.
Electrical rating
AFS-222, -262 300 VA pilot duty @ 115-277 VAC,
15A noninductive 277 VAC, 60 Hz 24 VAC @ 2.4A
AFS-460, -460-DSS 15A @ 125-277 VAC
1/4 HP @ 125 VAC
1/2 HP @ 250 VAC
1/2A @ 125 VDC
Max overpressure 0.5 psig (3.45 kPa)
Operating temp -40 to 18 F (-40 to 82 C)
Pressure line connection Ferrule and nut compression
for 1/4" OD tubing
Electrical connections Terminals
Approval/Recognition UL, FM, CSA, CE
Weight 2.0 (0.91 kg)
Life
AFS-222, -262 100,000 cycles minimum @ max overpressure and max electrical load
AFS-460, -460-DSS 6,000 cycles minimum @ max overpressure and max electrical load
|